HOME > PRODUCTS  >  CE Products Series >  Refrigerant Receivers

Refrigerant Receivers


Refrigerant Receivers
  Model :
 
Draw Type Connections Size Dimensions inches Volume (L) CE Cat.
In Out DIA øA B
a CR-101-2-CE 3/8" 1/4" 4.0 7.09 1.30 SEP
CR-101-3-CE 3/8" 3/8" 7.09 1.30
CR-102-CE 3/8" 3/8" 5.5 8.27 2.90
CR-103-CE 3/8" 3/8" 9.84 3.40
CR-104-CE 1/2" 1/2" 6.5 12.20 6.00
CR-105-CE 5/8" 5/8" 20.87 10.20
CR-106-CE 3/4" 3/4" 23.62 11.60
CR-107-CE 7/8" 7/8" 27.56 13.50
b CR-106-CE 3/4" 3/4" 6.5 23.62 11.60
CR-107-CE 7/8" 7/8" 27.56 13.50
Max . Permissible pressure: 31.03 bar , ( 450 psi ) / -10°C~+150°C Unit : inch
20.67 bar , ( 300 psi ) / -45°C~-10°C  

Type Dimensions ( inches ) lnlet / Outlet Volume (L) CE Cat.
DIA øA B C D Conn. lnlet Outlet
SCR-06-CE 6.50 21.00 4.00 7.87 1/4 3/4 3/4 10.60
SCR-07-CE 29.50 6.00 7.87 1/4 7/8 7/8 14.90
Max . Permissible pressure: 31.03 bar(450psi)  / -10°C~+150°C , 20.67 bar(300psi) / -45°C~-10°C
SCR-11-CE 8.50 25.00 5.00 9.65 1/4 1 1/8 1 1/8 21.20
Max . Permissible pressure: 31.03 bar(450psi)  / -10°C~+150°C , 20.67 bar(300psi) / -30°C~-10°C  

Application

We offer a complete line of horizontal and vertical high pressure liquid refrigerant receivers.  Receiver storage capacities are based on the liquid occupying no more than 90% of the internal volume when the temperature of the refrigerant is 40℃.  The receiver should be sized to hold the full system charge during service work, it should always be greater than the operating charge for all system components including the liquid lines.  It is essential that the maximum operating charge allows for fluctuating conditions.